Addison Cat5 Cabling,CAT 5 UTP cable,CAT 5 Ethernet Cable

 

 

Category 7 Cable

Application:155MbpsATM、 622MbpsATM、1000Base-T、10GBase-T.

Standard:According with the standard of IEC61156-5 CAT 7 and EN50288-4-1.

◎Cat7 Cable Construction Matrix:

STP
SFTP
Conductor
22/23AWG Solid Plain Copper
22/23AWG Solid Plain Copper
Insulation
Polyethylene
Polyethylene
Screen
Individual Aluminum Screen
Individual Aluminum Screen+Copper Wire Braid
Drain Wire
7/0.2mm
NIL
Outer Sheath
PVC/LSOH
PVC/LSOH

Frequency: 1-600MHz(common standard) 1-1000MHz(cat7E standard)
General Characteristics:
☆ Characteristic Impedance:100±15Ω (1-600MHZ).
☆ Nominal Velocity of Propagation:79%.
☆ Maxmium Mutual Capacitance:5.6nF/100m.
☆ Maximium DC Resistance: 22#:5.9Ω /100m 23#:7.5Ω /100m.
☆ Maxmium Resistance Unbalance:5%.
☆ Maxmium Propagation Delay Skew:30ns/100m.
☆ Maxmium Propagation Delay:536ns/100m@100MHz.
☆ Voltage Rating :60Vrms.
☆ Maximum Pulling Load:80N.
☆ Working Temperature:(-20)℃—(+60)℃.
☆ Storage Temperature:(-5)℃—(+50)℃.
☆ Flame Retardancy:IEC332-1(FRRVC&LSOH jacket)
  IEC332-1&IEC332-3C(LSFROH jacket).
Cat 7 Cable Parameters:

Construction
Coductor Diameter /mm
Diameter over Insulation
/mm
Pairs
Screen
Overall Diameter
/mm
Outer Sheath
SFTP
0.57/0.64
1.02
4
Individual Aluminum Screen+Copper Wire Braid
8/9.1
PVC/LSOH
SFTP
0.57/0.64
1.02
4
Individual Aluminum Screen+Copper Wire Braid
8.5/9.5
LSFROH
STP
0.57/0.64
1.02
4
Individual Aluminium Screen
8/9.1
PVC/LSOH
STP
0.57/0.64
1.02
4
Individual Aluminium Screen
8.5/9.5
LSFROH

Transmission Parameters:

FREQ

(MHZ)
NEXT
(db/100m)

Minimum Value/Typical Value/Standard Value
ATTENUATION

(db/100m)
RETURN LOSS
(db)
Minimum Value/Typical Value/Standard Value
PPACR
(db/100m)
Minimum Value/Typical Value/Standard Value
1
90.0/100.0/80.0
2.0
20.0/23.0/20.0
88.0/98.0/80.0
4
90.0/100.0/80.0
3.6
23.0/26.0/23.0
86.4/96.0/76.4
10
90.0/100.0/80.0
5.7
25.0/28.0/25.0
84.3/94.0/74.3
16
90.0/100.0/80.0
7.2
25.0/28.0/25.0
83.3/92.0/72.8
20
90.0/100.0/80.0
8.1
25.0/28.0/25.0
82.5/91.0/71.9
31.25
90.0/100.0/80.0
10.1
23.6/26.0/23.6
80.0/90.0/69.9
62.5
90.0/100.0/75.5
14.5
21.5/24.0/21.5
76.0/85.0/61.0
100
90.0/100.0/72.4
18.5
20.1/23.0/20.1
72.5/75.0/53.9
200
90.0/100.0/67.9
26.8
18.0/23.0/18.0
65.0/70.0/41.1
250
95.0/90.0/66.5
30.2
17.3/23.0/17.3
50.0/58.0/36.3
300
95.0/90.0/65.3
33.3
17.3/23.0/17.3
59.0/55.0/32.0
600
80.0/90.0/60.8
48.9
17.3/20.0/17.3
32.0/50.0/11.9

FREQ

(MHZ)
PPELFEXT
(db/100m)
Minimum Value/Typical Value/Standard Value
PSNEXT
(db/100m)
Minimum Value/Typical Value/Standard Value
PSACR
(db/100m)
Minimum Value/Typical Value/Standard Value
PSELFEXT
(db/100m)
Minimum Value/Typical Value/Standard Value
1

85.0/90.0/80.0

87.0/97.0/77.0
85.0/95.0/75.0
82.0/87.0/77.0
4
85.0/90.0/80.0
87.0/97.0/77.0
83.4/93.0/73.4
82.0/87.0/77.0
10
79.0/90.0/74.0
87.0/97.0/77.0
81.3/91.0/71.3
76.0/87.0/71.0
16
74.9/90.0/69.9
87.0/97.0/77.0
80.3/89.0/69.8
71.9/87.0/66.9
20
73.0/90.0/68.0
87.0/97.0/77.0
79.5/88.0/68.9
70.0/87.0/65.0
31.25
69.1/90.0/64.1
87.0/97.0/77.0
77.0/87.0/66.9
66.1/87.0/61.1
62.5
63.1/85.0/58.1
80.0/97.0/72.5
73.0/82.0/58.0
60.1/82.0/55.1
100
59.0/80.0/54.0
87.0/97.0/69.4
69.5/72.0/50.9
56.0/77.0/51.0
200
53.0/75.0/78.0
87.0/97.0/64.9
62.0/67.0/38.1
50.0/72.0/45.0
250
51.0/70.0/46.0
92.0/87.0/63.5
47.0/55.0/33.3
48.0/67.0/43.0
300
49.5/66.0/44.5
92.0/87.0/63.3
56.0/52.0/29.0
46.5/63.0/41.5
600
43.4/60.0/38.4
77.0/87.0/57.8
29.0/47.0/8.9
40.4/57.0/35.4

◎Cat7 Cable Ordering Information :

Part No.

Description

AD-BC-CAT7STP4PCM22 STP Cat7 22AWG 4Pairs,CM Grade(Non-Plenum )
AD-BC-CAT7STP4PCM23 STP Cat7 23AWG 4Pairs,CM Grade(Non-Plenum )
AD-BC-CAT7SFTP4PCM22 SFTP Cat7 22AWG 4Pairs,CM Grade(Non-Plenum )
AD-BC-CAT7SFTP4PCM23 SFTP Cat7 23AWG 4Pairs,CM Grade(Non-Plenum )
AD-BC-CAT7STP4PLH22 STP Cat7 22AWG 4Pairs,LSOH Grade(IEC332-1)
AD-BC-CAT7STP4PLH23 STP Cat7 23AWG 4Pairs,LSOH Grade(IEC332-1)
AD-BC-CAT7SFTP4PLH22 SFTP Cat7 22AWG 4Pairs,LSOH Grade(IEC332-1)
AD-BC-CAT7SFTP4PLH23 SFTP Cat7 23AWG 4Pairs,LSOH Grade(IEC332-1)
AD-BC-CAT7SFTP4PFRLH22 SFTP Cat7 22AWG 4Pairs,LSFROH Grade(IEC332-1&IEC332-3C)
AD-BC-CAT7SFTP4PFRLH23 SFTP Cat7 23AWG 4Pairs,LSFROH Grade(IEC332-1&IEC332-3C)

★Remark:
* CMR/CMP flame jacket can be offered according to customer request.
** Worst Values refer to the worst values measured in all the four pairs. Typical Values refer to average values taken from all the measurements for any pairs. Standard Values refer to the values as stipulated in the TIA/EIA standard. Typical Values are those margins that may likely be achieved during a normal testing. Worst Values are the margin taken from the worst pairs, which is the lowest margin that can be guaranteed for the cable. Usually, a typical measurement will have a better values than the Worst Value.

              [ ][Print this page]

 

Cabling System Manufacturer and a Cabling Solution Provider


Company Profile
| Distribution Policy | Products | Business Partners | Contact | links | link us | FAQ | News | site map | download
Copyright © 1991-2004 Addison Technology Ltd
webmaster@addison-tech.com